Skip to content
Dedicated export platform of the Ucursor group · Kunshan, Jiangsu, China sales@ucursor.com EN / 中文 / Рус
Request a quotation
Coolant distribution units (CDU) Model: GC40ALRA-01

40 kW In-Rack Air-to-Liquid CDU

16U high-capacity in-rack unit from the product catalogue.

Request a quotation All products in this series
40 kW In-Rack Air-to-Liquid CDU
Specifications

Technical specifications.

Cooling capacity 40 kW
Dimensions (D/W/H) 900 × 448 × 712 mm / 16U
Flow rate 43 LPM
Available head 1.5 bar
Approach temperature 15.0 °C
Max power consumption 4.5 kW
Power supply AC 220 V
Duty example Inlet 55 °C → outlet 39.5 °C, coolant PG-25

Request a quotation

Send us the model, specification or drawing. We respond with availability, certification documents and export options.